The capacitor and control gear are housed within a robust steel
enclosure which is suitable for either wall or floor mounting as
well as vertical stacking.
The equipment incorporates a special soft switching contactor arrangement
to minimise system disturbance which is caused by capacitor switching.
For example, a 50kVAr automatic step is controlled by two contactors
switching in cascade. These contactors incorporate a pre-connection
resistor system which reduces the effect of current inrush, thus
reducing system disturbance and increasing product life. 100 Amp
circuit fuses are installed to protect each 50kVAr capacitor step
and its associated control gear. On / off / auto switching can be
included if required.
The capacitor unit comprises the requisite number of individual
capacitor elements. These elements are manufactured from impregnated
metallized polypropylene and have a self-healing capability. Each
element incorporates a fail safe protection device.
For our standard 400 / 415 Volt capacitor products:
Voltage: 440V permanently
484V 8 hours per day
506V 30 minutes per day
528V 5 minutes per day
572V 1 minute per day
Current: 2 x In continuously @400V
Other products available upon request.
Ambient –40 to +60°c
Dielectric loss 0.2 Watts per kVAr
Total Capacitor losses 0.5 Watts per kVAr
Capacitor terminal voltage reduced to 50 Volts within 1 minute (exceeding
BS EN 60831)
RAL 7032 (Eurogrey) as standard. Alternative specifications supplied
upon request
PFC equipment manufactured to:
VDE 0560 part 41, BS EN 60831-1,
BS EN 61921, BS EN 60831-2.