Highly reliable, low loss capacitors with self healing properties
Safety protection system incorporated within each capacitor element
Internally extendible and maintainable
Floor standing units for easy installation
The Vector FS series is ideally situated where floor space is limited
Soft Switching contactors for minimal system disturbance
Also available with harmonic blocking or filter reactors
Multi-stage switching with on/off/auto facility available on the
control relay
Panel mounted on/off/auto switches and indicator lamps available
as low cost option
A suitably rated switch-fuse, circuit-breaker or loadbreak switch
is available as an option where required
The enclosure is of robust steel construction and is designed for
total front access via a hinged door. Top or side cable entry is
provided as standard. Bottom cable entry is also available upon
request. The unit utilises an SBA type modular equipment tray system.
Each equipment tray includes the requisite
capacitors, soft switching contactors, auxiliary and control fuses.
This system greatly simplifies modification or upgrade.
The equipment incorporates a special soft switching contactor arrangement
to minimise system disturbance which is caused by capacitor switching.
For example, a 50kVAr automatic step is controlled by two contactors
switching in cascade. These contactors incorporate a pre-connection
resistor system which reduces the effect of current inrush, thus
reducing system disturbance and increasing product life. 100 Amp
circuit fuses are installed to protect each 50kVAr capacitor step
and its associated control gear.
The capacitor unit comprises the requisite number of individual
capacitor elements. These elements are manufactured from impregnated
metallized polypropylene or metallized paper and plastic film and
have a self-healing capacity. Each one incorporates a fail-safe
protection device.
For our standard 400 / 415 Volt capacitor products:
Voltage: 440V permanently
484V 8 hours per day
506V 30 minutes per day
528V 5 minutes per day
572V 1 minute per day
Current: 2 x In continuously @400V
Other products available upon request.
Ambient –40 to +60°c
Dielectric loss 0.2 Watts per kVAr
Total Capacitor losses 0.5 Watts per kVAr
Capacitor terminal voltage reduced to 50 Volts within 1 minute (exceeding
BS EN 60831)
RAL 7032 (Eurogrey) as standard.Alternative specifications supplied
upon request
PFC equipment manufactured to:
VDE 0560 part 41, BS EN 60831-1,
BS EN 61921, BS EN 60831-2.