These automatic modules are designed to fit into existing switchgear,
control panels or pre-installed Power Factor Correction units.
Control is provided automatically, via an independent or existing
Power Factor control relay.
The equipment incorporates a soft-switching contactor arrangement
to minimise system disturbance caused by capacitor switching.
A pre-connection resistor system is integrated within the contactors,
which reduces the effect of current inrush to a minimum.
Highly reliable, low loss capacitors with self healing properties
Safety protection system built into each capacitor element
Modular capacitor tray arrangement
The desired kVAr rating is built up in step sizes as required by
the customer
The interconnection of trays is achievable with minimal wiring
requirements
Main and control fusing as standard
Capacitor modules can be designed specifically to suit the customers
required dimensions and ratings
Static Power Factor Correction modules for placement within an
existing control panel, switchgear cubicle or Power Factor Correction
unit.
These modules can be independently switched, if required, via customers
own controlgear.
Highly reliable, low loss capacitors with self healing properties
Safety protection system incorporated into each capacitor element
For switchgear and control panel manufacturers wishing to install
Power Factor Correction within their own enclosures
Desired kVAr rating can be built up in step sizes dictated by the
customer’s own requirements
Custom built capacitor trays designed for special applications
Terminal blocks or flying leads and fixing holes provided for ease
of installation
These modules are specifically designed for customers who wish to
integrate Power Factor Correction within switchgear or control cubicles.
The low losses associated with these capacitors allow the units
to be contained within their own enclosure. This is applicable for
installations in extreme or dusty atmospheres.
The capacitor unit is constructed from the required number of individual
capacitor elements. These elements are manufactured from impregnated
metallized polypropylene and have a self-healing capability. Each
element incorporates a fail-safe protection device and discharge
resistors.
For our standard 400 / 415 Volt capacitor products:
Voltage: 440V permanently
484V 8 hours per day
506V 30 minutes per day
528V 5 minutes per day
572V 1 minute per day
Current: 2 x In continuously @400V
Other products available upon request.
Ambient –40 to +60°c
Dielectric loss 0.2 Watts per kVAr
Total Capacitor losses 0.5 Watts per kVAr
Capacitor terminal voltage reduced to 50 Volts within 1 minute (exceeding
BS EN 60831)
RAL 7032 (Eurogrey) as standard. Alternative specifications supplied
upon request.
Rated at 415 Volts 3 phase 50 Hertz. Up to 162 kVAr per module as
standard.
PFC equipment is manufactured to:
VDE 0560 part 41, BS EN 60831-1,
BS EN 61921, BS EN 60831-2.